The S7-PM1207 is a power supply module manufactured by Siemens, specifically designed for use with the Siemens S7-1200 Programmable Logic Controller (PLC) systems. This module provides a stable and reliable DC output voltage, ensuring the proper operation of connected devices and components in industrial automation applications. Its compact design and robust performance make it an essential component for powering automation systems in various industries.








| Parameter | Value |
|---|---|
| Input Voltage Range | 85–264 VAC (47–63 Hz) |
| Output Voltage | 24 VDC |
| Output Current | 2.5 A |
| Power Output | 60 W |
| Efficiency | > 90% |
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Dimensions (W x H x D) | 70 mm x 100 mm x 75 mm |
| Weight | Approximately 0.4 kg |
| Certifications | CE, UL, cULus, and RoHS |
The S7-PM1207 module features screw terminals for input and output connections. Below is the pin configuration:
| Terminal Label | Description |
|---|---|
| L | Live AC input (85–264 VAC) |
| N | Neutral AC input |
| PE | Protective Earth (Ground) |
| Terminal Label | Description |
|---|---|
| +24V | Positive DC output (24 VDC) |
| 0V | Negative DC output (Ground) |
L, N, and PE).+24V terminal to the positive input of the load (e.g., PLC, sensors).0V terminal to the ground of the load.PE terminal to the protective earth to ensure safety and reduce electrical noise.The S7-PM1207 is commonly used to power Siemens S7-1200 PLC systems. Below is an example of how to connect the power supply to the PLC:
+24V terminal of the S7-PM1207 to the L+ terminal of the S7-1200 PLC.0V terminal of the S7-PM1207 to the M terminal of the S7-1200 PLC.| Issue | Possible Cause | Solution |
|---|---|---|
| No output voltage | Input power not connected or faulty | Verify AC input connections and voltage. |
| Output voltage is unstable | Overload or short circuit on the output | Reduce the load or check for short circuits. |
| Module overheating | Insufficient ventilation or high ambient temperature | Improve airflow or reduce ambient temperature. |
| PLC not powering on | Incorrect wiring or insufficient output current | Verify connections and ensure load is within limits. |
Q1: Can the S7-PM1207 power multiple devices simultaneously?
A1: Yes, as long as the total current draw does not exceed 2.5 A. Use proper wiring to distribute the power.
Q2: Is the S7-PM1207 suitable for outdoor use?
A2: The module is not designed for direct outdoor use. If outdoor installation is required, ensure it is housed in a weatherproof enclosure.
Q3: What happens if the input voltage exceeds 264 VAC?
A3: The module may shut down or get damaged. Always ensure the input voltage is within the specified range.
Q4: How do I reset the module after a short circuit?
A4: Disconnect the load, resolve the short circuit, and then reconnect the load. The module will automatically recover.
Q5: Can I use the S7-PM1207 with non-Siemens devices?
A5: Yes, the S7-PM1207 can power any device requiring 24 VDC, provided the current draw is within the 2.5 A limit.